Skip to content

The Healthcare Facility Manager’s EPSS Maintenance & Testing Checklist

The Healthcare Facility Manager’s EPSS Maintenance & Testing Checklist

Stay Compliant, Stay Survey-Ready

This checklist provides a framework for the routine maintenance and testing required to keep your Emergency Power Supply System (EPSS) reliable and your documentation in order for NFPA 110 and The Joint Commission (TJC) compliance.

Disclaimer: This is a general guide. It is not a substitute for the specific recommendations of your generator’s manufacturer or the work of a certified technician.

Weekly Walk-Around Inspection

CategoryTask / Check ItemStatusNotes
Generator AreaArea is clean, dry, and free of obstructions.
Generator AreaNo signs of fluid leaks (fuel, oil, coolant).
Engine & FluidsEngine oil level is within the normal range.
Engine & FluidsEngine coolant level is within the normal range.
Engine & FluidsBlock heater is operational (engine block is warm).
Fuel SystemDay tank and main storage tank fuel levels are adequate.
Starting SystemBattery charger is operational and indicating “Float Charge.”
Starting SystemBattery terminals are clean and free of corrosion.
Controller / ATSGenerator controller is in “Auto” mode.
Controller / ATSNo active alarms or warnings are displayed.
Controller / ATSAutomatic Transfer Switch (ATS) is in its normal position.

Monthly Transfer Test

ParameterRequirementResult / Value
Perform full Weekly Walk-Around InspectionCompleted
Notify relevant hospital staff of the testCompleted
Time to StartN/A
Time to Transfer≤ 10 seconds
Total Run Time≥ 30 minutes
kW Output (% of Nameplate)≥ 30%
Voltage Output (V)Normal Range
Frequency (Hz)Normal Range
Oil Pressure (PSI)Normal Range
Coolant Temperature (°F)Normal Range
Post-Test: Verify return to “Auto” modeCompleted
Post-Test: Top off fuel tank(s)Completed

Quarterly Inspection

CategoryTask / Check ItemStatusNotes
PrerequisitePerform all tasks from the Weekly and Monthly checklists.
MechanicalInspect engine belts and hoses for cracks, fraying, or wear.
MechanicalInspect exhaust system for leaks, damage, or corrosion.
MechanicalInspect air filter and intake piping for blockages or damage.
Battery ServiceCheck specific gravity of battery electrolyte (if applicable).
Battery ServicePerform a battery load test.

Still have questions or looking for more information?

Generator Source specializes in low-hour, used, new, and surplus generator sets. We have a wide variety of generator sizes and models to fit any project. We are not a broker, we own what we sell.
Call us today (877-866-6895) or click Contact Us to be connected with one of our experienced sales reps. 
We have 350+ generators in stock and ready to ship!

Still have questions or looking for more information?