Industrial Generator FAQ (Frequently Asked Questions)

At Generator Source, we receive many inquiries about electrical, engine, and generator-related topics. To assist our customers and website visitors, we’ve compiled this FAQ covering the most common questions we encounter. This list will be updated regularly based on customer feedback and new developments. If you have additional questions you’d like to see here, please contact us, and we’ll do our best to answer and incorporate them.


1. What is a power factor?

The power factor (pf) is the ratio of real power (kW) to apparent power (kVA). It reflects how efficiently the generator transfers power to the load:

  • Higher pf = Greater efficiency.
  • Standard industrial generator pf = 0.8.

For example, if a generator produces 500 kW of real power and 625 kVA of apparent power, the pf is: 0.8=5006250.8 = \frac{500}{625}0.8=625500​


2. If I am interested in a generator that is not the voltage I need, can the voltage be changed?

Yes, but it depends on the generator’s design:

  • Reconnectable Generators: Voltage can be changed.
    • 12-lead: Can switch between three-phase and single-phase (reduced output in single-phase).
    • 10-lead: Limited to three-phase voltages.
  • Non-Reconnectable Generators: Voltage cannot be changed.

3. What does an Automatic Transfer Switch do?

An Automatic Transfer Switch (ATS):

  • Monitors utility power and automatically switches to the generator during an outage.
  • Switches back to utility power when it’s restored.
  • Commonly used in environments requiring high availability, like data centers or hospitals.

4. Can a generator I am looking at parallel with one I already own?

Yes, generators can be paralleled:

  • For Redundancy or Increased Capacity: Identical generators are easier to parallel.
  • Different Generators: Paralleling requires careful design and consideration of engine configuration, generator design, and voltage regulators.

5. Can you convert a 60 Hz generator to 50 Hz?

Most commercial generators can be converted:

  • General Rule: 60 Hz machines run at 1800 RPM; 50 Hz machines run at 1500 RPM.
  • Conversion involves adjusting the engine RPM. Some cases may require part replacements or modifications.

6. How do I determine what size Generator I need?

Proper sizing is critical to prevent damage to the generator or connected devices:

  • Key Considerations: Power load requirements, prime vs. standby usage, and application specifics.
  • Use our Sizing a Generator article or consult our experts for detailed guidance.

This FAQ is designed to provide a foundation for understanding industrial generators. For more detailed discussions or assistance, please contact us directly!

More Industrial Generator Questions

What is an industrial generator?

An industrial generator is a robust power system designed to provide continuous or backup electricity for large-scale operations like manufacturing plants, data centers, hospitals, and major commercial facilities, ensuring power reliability and business continuity.

What is the difference between an industrial and commercial generator?

While often used interchangeably, industrial generators typically offer higher power outputs (MW range), greater durability, and are built for demanding, continuous-duty cycles in critical environments. Commercial generators are generally smaller (kW range) and suited for general business backup like offices or retail.

How do industrial generators work?

Industrial generators convert mechanical energy into electrical energy. An internal combustion engine (fueled by diesel, natural gas, or propane) drives an alternator. The alternator’s rotating magnetic field induces an electrical current, which is then regulated and distributed as usable power.

What are the main types of fuel used for industrial and commercial generators?

Common fuel types include diesel, natural gas, and propane. Diesel offers high energy density and immediate power. Natural gas provides cleaner emissions and continuous supply if connected to a utility line. Propane is good for long-term storage and portability. Bi-fuel or dual-fuel options combine these.

What are the common power ratings for generators (kW vs. kVA)?

kW (kilowatts) represents the “real power” or usable power output consumed by equipment. kVA (kilovolt-amperes) is “apparent power,” which includes both real and reactive power. The relationship is kW=kVA×PowerFactor, where a typical power factor for industrial generators is 0.8.

What is an Automatic Transfer Switch (ATS) and why is it important?

An ATS is a critical component that automatically detects a power outage from the utility grid, signals the generator to start, and seamlessly transfers the electrical load to the generator. Once utility power is restored, it transfers the load back and shuts down the generator, ensuring uninterrupted power.

What is the difference between standby, prime, and continuous power ratings?

Standby power is for emergency use during utility outages (limited runtime, e.g., 200 hours/year). Prime power is for continuous operation with variable loads (unlimited runtime, 10% overload capability for 1 hour out of 12). Continuous power is for constant loads with unlimited runtime and no overload capability, often for isolated grids.

How do I determine the right size generator for my business?

Proper sizing involves a detailed load analysis, calculating your facility’s peak and average power requirements (kW and kVA), considering starting current (inrush current) for motors, and future expansion. It’s crucial to consult with a professional to avoid oversizing or undersizing.

How long can an industrial generator run continuously?

Many industrial generators, especially those rated for prime or continuous power, are designed for prolonged operation, often running for days or even weeks given sufficient fuel supply and proper maintenance intervals. Standby generators have more limited continuous run time specifications.

What maintenance does a commercial generator require?

Regular preventative maintenance is vital. This includes daily/weekly visual inspections (fluid levels, leaks), monthly checks (battery, fuel system, belts, hoses), quarterly fluid and filter changes (oil, fuel, air), and annual comprehensive inspections including load bank testing and electrical system diagnostics.

Can I install a commercial generator myself?

For commercial and industrial generators, professional installation by licensed electricians, certified generator technicians, and sometimes mechanical contractors is essential. This ensures proper wiring, fuel line connection, adherence to local codes (NEC), warranty validity, and safe, compliant operation.

What are common applications for industrial and commercial generators?

They are critical for healthcare facilities (hospitals, clinics, labs), data centers, manufacturing plants, telecommunications, retail complexes, municipal services (water treatment, emergency operations), construction sites, agricultural operations, and remote power requirements.

Are generators noisy? How can noise be mitigated?

Unenclosed generators can be very loud. Noise mitigation involves sound-attenuated enclosures (soundproof housings), critical-grade silencers for exhaust, vibration isolation mounts, and strategic placement away from noise-sensitive areas or residential zones.

What is a load bank test and why is it important for generators?

A load bank test involves connecting a resistive, reactive, or combined electrical load to the generator, forcing it to operate at or near its full rated capacity for a specified duration. This verifies performance, prevents “wet stacking” (unburnt fuel accumulation), and identifies potential issues under stress.

What are the benefits of having a backup generator for my business?

Key benefits include preventing operational downtime, protecting valuable equipment and data from power surges/outages, maintaining productivity, ensuring employee and customer safety, complying with critical service regulations, and guaranteeing business continuity during grid failures.

What is “wet stacking” and how can it be prevented?

Wet stacking occurs in diesel generators when they operate consistently at very light loads, leading to incomplete combustion, unburnt fuel accumulation in the exhaust system, and carbon buildup. It’s prevented by periodic load bank testing, which burns off these deposits and cleans the engine.

What is the typical lifespan of an industrial generator?

With proper installation, regular maintenance, and appropriate sizing for its application, an industrial generator can last 20 to 30 years or more, with engine rebuilds extending life even further. Hours of operation are a better indicator of wear than calendar age.

What is the difference between single-phase and three-phase power?

Single-phase power is typically found in residential and small commercial applications (e.g., 120/240V). Three-phase power provides a more consistent, smoother power delivery and is standard for industrial and large commercial applications due to its efficiency in powering large motors and heavy machinery (e.g., 208V, 480V, 600V).

What are the key components of an industrial generator system?

Core components include the engine, alternator (generator end), fuel system, cooling system, exhaust system, lubrication system, control panel, and the automatic transfer switch (ATS). Optional components include sound-attenuated enclosures, remote monitoring, and larger fuel tanks.

What safety considerations are paramount when operating a generator?

Safety considerations include proper ventilation (for exhaust), adequate clearance, proper grounding, fuel handling precautions, electrical lockout/tagout procedures, fire suppression systems, regular inspections, and ensuring trained personnel operate and maintain the unit.

How does remote monitoring for generators work?

Remote monitoring systems use sensors and telematics to collect data on generator status (run time, fuel levels, fault codes, battery voltage, oil pressure, coolant temperature). This data is transmitted via cellular or satellite to a central system, allowing owners/operators to monitor performance and receive alerts remotely.

What are the environmental regulations for industrial generators?

Regulations vary by location but often include emissions standards (EPA Tier levels for diesel engines), noise pollution limits, fuel storage requirements, and waste disposal guidelines. Compliance is critical and often requires specialized permits and monitoring.

What is generator paralleling and why is it used?

Generator paralleling involves connecting two or more generators to operate simultaneously, sharing the electrical load. This provides redundancy, increased capacity, better fuel efficiency (by running only what’s needed), and easier maintenance by allowing one generator to be serviced while others run.

When should I consider a natural gas generator over a diesel generator?

Natural gas generators are often preferred for cleaner emissions, direct connection to utility lines (eliminating fuel storage logistics), and quieter operation. Diesel generators are chosen for their higher power density, quicker startup, and better performance in extreme conditions where natural gas lines aren’t available.

What is the importance of generator grounding?

Proper grounding of a generator system is crucial for safety, providing a safe path for fault currents in the event of an electrical short or lightning strike, protecting personnel from electric shock, and preventing damage to the equipment.

What is generator derating?

Generator derating refers to the reduction in a generator’s rated power output due to environmental factors like high altitude, high ambient temperature, or high humidity. These conditions reduce engine efficiency and alter alternator performance.

What is the role of a generator control panel?

The control panel is the “brain” of the generator, providing operational data, diagnostic information, and controls. It monitors engine parameters (oil pressure, temperature), generator output (voltage, frequency), manages auto-start/stop functions, and displays fault codes.

What are common types of generator enclosures?

Enclosures protect the generator from weather and reduce noise. Types include open-skid (no enclosure), weather-proof enclosures (basic protection), and sound-attenuated or “silent” enclosures (significant noise reduction). Walk-in enclosures offer space for maintenance inside.

How does fuel polishing benefit diesel generators?

Fuel polishing removes water, sediment, and microbial growth (diesel bug) from the fuel tank, preventing clogged filters, injector damage, and engine problems, especially important for stored diesel fuel in backup generators.

What’s the difference between air-cooled and liquid-cooled generators?

Air-cooled generators use fans to force air over the engine to cool it, typically found in smaller residential/light commercial units. Liquid-cooled generators use a radiator and coolant system, like a car engine, and are standard for larger industrial and commercial generators due to their superior cooling capacity and durability.

What are common generator fault codes and what do they indicate?

Common fault codes include low oil pressure, high engine temperature, overspeed, underspeed, overcrank, low coolant level, battery charger failure, and overcurrent. Each code indicates a specific issue requiring attention to prevent damage or downtime.

How important is a comprehensive warranty for a generator?

A comprehensive warranty provides peace of mind and financial protection against manufacturing defects or premature component failure. Understanding the terms, coverage period, and service agreements is crucial when purchasing a generator.

Can I buy a used industrial generator? What are the considerations?

Yes, buying used can be cost-effective. Considerations include verifying the generator’s history (service records, runtime hours), conducting a thorough inspection (engine, alternator, controls), performing a load bank test, and understanding the remaining lifespan. Buy from reputable dealers.

What is a Tier 4 Final generator?

Tier 4 Final refers to the strictest emissions standards set by the EPA for off-road diesel engines. Generators meeting these standards use advanced technologies like Selective Catalytic Reduction (SCR) and Diesel Particulate Filters (DPF) to significantly reduce harmful emissions.

What electrical protections are typically integrated into a generator system?

Integrated protections include circuit breakers (overcurrent protection), ground fault interrupters (GFI), voltage regulators (over/under voltage), frequency regulators (over/under frequency), and phase rotation protection to prevent electrical damage.

What is the difference between synchronous and asynchronous alternators?

Most industrial generators use synchronous alternators due to their ability to maintain a constant output frequency regardless of load changes, essential for stable power. Asynchronous (induction) alternators are simpler but less common for prime power generation, often used in smaller, less critical applications.

How important is fuel quality for generator performance?

Extremely important. Poor fuel quality (contaminated, old, or incorrect type) can lead to engine issues, clogged filters, reduced efficiency, increased emissions, and premature component wear. Regular fuel testing and polishing are recommended for stored fuel.

What steps are involved in generator startup and shutdown procedures?

Startup involves pre-start checks (fluids, fuel, battery), activating the control panel, and allowing a brief warm-up. Shutdown includes reducing load, cooling down the engine (idle time), and then safely turning off the unit and performing post-shutdown checks. Automatic systems manage this.

What is the role of a voltage regulator in a generator?

The voltage regulator (Automatic Voltage Regulator – AVR) senses the generator’s output voltage and adjusts the exciter current to maintain a consistent and stable voltage output, crucial for protecting connected equipment from voltage fluctuations.

How does elevation affect generator performance?

As elevation increases, the air density decreases, leading to less oxygen for combustion. This results in “derating” – a reduction in the engine’s power output and potentially higher fuel consumption for the same load. Generators must be sized with elevation in mind.

What is the significance of the generator’s frequency (Hz)?

Frequency (typically 50 Hz or 60 Hz) indicates the rate at which the alternating current (AC) changes direction. Maintaining the correct frequency is vital as most electrical equipment is designed for a specific frequency. Deviations can cause equipment malfunction or damage.

Can a generator be rented for temporary power needs?

Yes, generator rentals are a common solution for temporary power needs, such as construction projects, events, emergency outages, or during planned maintenance of primary power systems. Rental options range from small portable units to large industrial-grade generators.

What are the advantages of modular generator systems?

Modular systems use multiple smaller generators that can be paralleled. Advantages include scalability (add/remove capacity as needed), increased reliability through redundancy, better fuel efficiency at varying loads, and easier maintenance (one unit can be serviced while others operate).

How does temperature affect generator performance?

High ambient temperatures can cause the engine to run hotter, potentially leading to derating (reduced power output) and increased cooling system strain. Extremely low temperatures can affect starting capability, fuel flow, and battery performance, requiring cold weather kits.

What is the importance of a generator’s fuel tank capacity?

Fuel tank capacity directly determines the generator’s continuous run time without refueling. For critical applications, a larger tank or external fuel supply system is essential to ensure extended operation during prolonged outages.

What types of sensors are typically found on an industrial generator?

Common sensors monitor engine parameters (oil pressure, coolant temperature, engine speed, fuel level), electrical output (voltage, current, frequency), and environmental conditions (exhaust temperature, vibration). These feed data to the control panel.

What is the role of a generator’s battery?

The battery provides the necessary power to start the generator engine. A healthy, fully charged battery is critical for reliable automatic starting, especially in standby applications. Battery chargers are integrated to keep it topped up.

How can I prevent generator theft?

Prevention measures include securing the generator within a fenced area, using heavy-duty locks (wheel, hitch, or fuel cap locks), installing GPS tracking devices, using security cameras, and placing the unit in a well-lit, visible location.

What is GENSIS and how does it relate to generators?

GENSIS (Generator Set Intelligent System) is a term often used to describe advanced, integrated control systems found in modern generators. These systems offer sophisticated monitoring, diagnostics, and communication capabilities for optimal performance and management.

What is a “wet exhaust” system in a generator?

A wet exhaust system (common in marine generators or some specialized industrial applications) cools exhaust gases by injecting water into the exhaust stream. This reduces exhaust temperature and noise, but it requires careful design to prevent water from backing up into the engine.

How often should diesel fuel be checked and treated for long-term storage?

For critical backup applications, diesel fuel should be checked every 3-6 months for contamination (water, sediment, microbial growth) and treated with fuel stabilizers, biocides, and conditioners as needed to maintain quality and prevent degradation over 12-24 months.

What is the significance of the exhaust system in a generator?

The exhaust system safely vents hot, toxic exhaust gases away from the generator and surrounding areas. It includes manifold, muffler (silencer), and piping. Proper sizing and routing are critical for engine performance, safety, and noise control.

What is the concept of generator load shedding?

Load shedding is a technique where non-critical electrical loads are automatically disconnected when the generator is under heavy demand or if an issue occurs. This ensures that critical loads remain powered and prevents generator overload or shutdown.

What are the primary causes of generator failure?

Common causes include lack of preventative maintenance (e.g., old fuel, dead battery), component wear and tear, incorrect sizing, fuel system issues, cooling system problems, electrical faults, and neglecting to perform load bank testing.

How do I ensure environmental compliance with my generator?

Ensuring compliance involves selecting generators that meet current emissions standards (e.g., Tier 4 Final), implementing proper fuel storage and spill prevention plans, managing waste (filters, fluids), and adhering to local noise and air quality regulations. Regular reporting may also be required.

What role does a generator’s cooling system play?

The cooling system (typically radiator, fan, water pump, coolant) is crucial for maintaining the engine’s optimal operating temperature. Overheating can lead to engine damage, while under-cooling can reduce efficiency.

What are some key considerations for generator security?

Security measures include physical barriers (fencing, robust enclosures), locks (fuel cap, control panel), alarm systems, GPS tracking, and ensuring the generator is not easily accessible to unauthorized personnel.

What is the benefit of a used generator from a reputable dealer versus a private sale?

A reputable dealer typically provides thoroughly inspected, serviced, and often reconditioned units, sometimes with a limited warranty. They also offer expertise in sizing, installation, and ongoing support, which private sales rarely provide, significantly reducing risk.

What is a generator paralleling switchgear?

Paralleling switchgear is a sophisticated control system that manages the synchronization and load sharing between multiple generators operating in parallel. It ensures stable power delivery, protects the generators, and optimizes fuel efficiency.

What is the difference between open-skid and enclosed generators?

Open-skid generators are mounted on a frame with no protective housing, suitable for indoor installations or dedicated generator rooms. Enclosed generators have a weather-resistant or sound-attenuated canopy, making them suitable for outdoor installation and noise reduction.

How does a generator integrate with a facility’s electrical system?

Integration involves connecting the generator’s output to the facility’s main electrical panel or a sub-panel, usually via an Automatic Transfer Switch (ATS). This ensures seamless transition of power during outages and isolates the generator from the utility grid for safety.

What are common misconceptions about industrial generators?

Common misconceptions include thinking they require no maintenance, can run indefinitely without refueling, are always excessively loud, or that sizing is a simple calculation. Proper understanding of maintenance, fuel needs, noise mitigation, and professional sizing is crucial.

What is the process for generator removal and decommissioning?

Generator removal and decommissioning involve safely disconnecting all electrical and fuel lines, draining fluids (oil, coolant, fuel), properly handling hazardous waste, disassembling the unit, and transporting it according to environmental regulations.

How does a generator’s control system communicate with building management systems (BMS)?

Modern generator control systems can integrate with BMS platforms via standard communication protocols like Modbus, BACnet, or Ethernet. This allows for centralized monitoring, alarm notification, and remote control from the facility’s overall building management system.

What are the benefits of predictive maintenance for generators?

Predictive maintenance uses data analytics and sensor readings to anticipate potential failures before they occur. This reduces unscheduled downtime, optimizes maintenance schedules, extends component life, and lowers overall operating costs compared to reactive maintenance.

What are typical generator warranty exclusions?

Warranty exclusions often include damage from improper installation, lack of maintenance, unauthorized modifications, misuse, natural disasters, or the use of non-approved parts or fluids. Understanding these exclusions is vital.

What are the options for used generator reconditioning?

Reconditioning can range from basic cleaning and fluid changes to comprehensive engine overhauls, alternator rewinds, control panel upgrades, and cosmetic refurbishment. The level of reconditioning depends on the generator’s condition and the buyer’s needs.